- Clear diagnostics and start dynamic monitoring.
- Alternate Open and Close commands while observing the physical IED, an independent IEC 61850 client, and ArIED Live Monitor.
- Live Monitor must change immediately from command-confirmed feedback.
- A matching
dchgreport must then logevent-driven report confirmed command feedbackwithin two seconds. - The monitor must not roll back to an older state from a stale report frame.
- If event delivery is missing, diagnostics must report
no matching dchg report arrived within 2 secondsinstead of silently waiting for MMS validation.